Data Center Water Usage: How Much Water Data Centers Use, Why, and What It Means for Compliance

How much water data centers use and why, WUE, direct vs indirect use, water sources, ways to cut use, and the compliance each source brings. Sourced data.

Short answer: U.S. data centers consumed about 66 billion liters (about 17 billion gallons) of water on site in 2023, according to Lawrence Berkeley National Laboratory (LBNL), up from 21.2 billion liters in 2014. Most of that water evaporates in cooling towers and evaporative coolers. The water used to generate their electricity is far larger, at nearly 800 billion liters in 2023. Where the water comes from matters as much as how much is used. Potable water, recycled water, and groundwater each come with their own permits, backflow protection, and testing duties.

Last reviewed October 30, 2026. Every figure below comes from a report listed in Sources at the end.

How much water do data centers use?

The most complete national estimate is LBNL’s 2024 United States Data Center Energy Usage Report, supported by the U.S. Department of Energy. It models every U.S. data center by type, cooling system, and climate.

Measure Figure Source
Direct (on-site) water consumption, 2014 21.2 billion liters LBNL 2024
Direct (on-site) water consumption, 2023 66 billion liters (about 17.4 billion gallons) LBNL 2024
Share of 2023 direct use in hyperscale and colocation facilities 84% LBNL 2024
Projected direct use by hyperscale data centers alone, 2028 60 to 124 billion liters LBNL 2024
Indirect water (power generation), 2023 Nearly 800 billion liters LBNL 2024
Electricity use, 2023 176 TWh, 4.4% of U.S. electricity LBNL 2024
Projected electricity use, 2028 About 325 to 580 TWh, 6.7% to 12.0% of U.S. electricity LBNL 2024

Company reports show the same growth at the operator level. Google reported 10.5 billion gallons of water consumed by its data centers worldwide in 2025 (13.6 billion gallons withdrawn, 3.0 billion gallons discharged). Its total water consumption, including offices, rose 34% from 2024 to 2025. A single campus can be large: Google’s Council Bluffs, Iowa, site consumed about 1.35 billion gallons in 2025, and its campuses in The Dalles, Oregon, consumed 469 million gallons.

Where sources disagree: national estimates depend on method and year. A peer-reviewed study by Siddik, Shehabi, and Marston (Environmental Research Letters, 2021) put the total operational water footprint of U.S. data centers in 2018 at 5.13 × 10⁸ cubic meters (513 billion liters), counting both on-site and power plant water. LBNL’s 2023 figures (66 billion liters direct plus nearly 800 billion indirect) use a newer model and a later year. Treat any single national number as an estimate, not a meter reading.

Why do data centers use so much water?

Servers turn the electricity they use into heat, and evaporating water is an energy-efficient way to reject it.

Cooling towers. In a water-cooled chiller plant, warm water from the chillers runs over a cooling tower, and part of it evaporates. The U.S. Department of Energy’s Federal Energy Management Program (FEMP) explains that tower make-up water equals evaporation plus blowdown plus drift:

  • Evaporation is how the tower rejects heat.
  • Blowdown is water drained on purpose, because evaporation leaves dissolved minerals behind and they have to be flushed out before they cause scale and corrosion.
  • Drift is mist carried out of the tower. It is small and controlled with drift eliminators.

Evaporative and adiabatic cooling. Many large facilities cool with outside air most of the year and add water only on hot days, either by spraying it into the air stream (adiabatic cooling) or by wetting media. LBNL found that facilities using water-cooled chillers without economizers have the highest water use, largely from cooling tower water, while airside economizers with occasional adiabatic cooling use very little.

Humidity control. Meta’s 2025 Sustainability Report notes that most water use in its data centers goes to managing air flow, temperature, and humidity in the server halls.

Growth ahead. LBNL projects that average on-site water intensity will rise after 2023, reflecting higher WUE in hyperscale and colocation data centers and more water use by liquid-cooled systems.

What is WUE (water usage effectiveness)?

WUE is the standard metric for data center water efficiency. It was introduced by The Green Grid as a companion to power usage effectiveness (PUE). As LBNL defines it, WUE is the data center’s water consumption divided by the electricity used by its IT equipment, reported in liters per kilowatt-hour (L/kWh).

There are two versions:

  • Site WUE counts only water used at the facility, mostly for cooling.
  • Source WUE adds the water consumed to generate the facility’s electricity.
WUE figure Value Source
U.S. average site WUE, through 2023 Just over 0.36 L/kWh LBNL 2024
U.S. average site WUE, projected after 2023 0.45 to 0.48 L/kWh LBNL 2024
Reported by some hyperscale facilities using airside economizers with adiabatic assist 0.1 to 0.3 L/kWh LBNL 2024
Microsoft fleet average, fiscal year 2024 0.30 L/kWh (down 39% from 0.49 in 2021) Microsoft
Water consumed per kWh of electricity supplied to U.S. data centers (indirect), 2023 4.52 L/kWh LBNL 2024

A low site WUE is not automatically better. LBNL notes that water-cooled systems are generally more energy efficient than air-cooled chillers, which use no water but more electricity. Since power plants also consume water, a facility that saves water on site can raise its indirect water use.

Direct vs indirect water use

Direct (on-site) Indirect (off-site)
What it is Water the facility withdraws and consumes, mostly in cooling Water consumed at power plants that generate the facility’s electricity
U.S. total, 2023 66 billion liters Nearly 800 billion liters
Main drivers Cooling system type, climate, operating practices Grid fuel mix and power plant cooling
Metric Site WUE Source WUE

Nationally, the indirect footprint is roughly 12 times the direct one. But direct use is local: it comes out of the watershed and utility system where the facility sits. Siddik and colleagues found that about one-fifth of U.S. data center servers’ direct water footprint comes from moderately to highly water-stressed watersheds, and nearly half of servers are fully or partly powered by plants in water-stressed regions. Google reports that 13% of its 2025 freshwater withdrawals came from sources at high risk of depletion or scarcity, and 15% from sources at medium risk.

Where does data center water come from?

Most data centers buy potable (drinking) water from the local public water system. Google’s 2025 data is a useful example of the mix: of 13.6 billion gallons withdrawn by its data centers, about 10.9 billion gallons (81%) was potable water, 1.7 billion gallons was other non-potable water, and 0.9 billion gallons was reclaimed wastewater.

Source How it is used Watch-outs
Potable water from a public water system Cooling tower make-up, humidification, domestic use, fire service Competes with community supply; backflow protection at every connection
Recycled (reclaimed) water Cooling tower make-up where approved Separate piping, use-site approval, cross-connection testing
Groundwater from an on-site well Cooling, and sometimes drinking water for staff A campus well can make the operator a regulated public water system
Other non-potable water Cooling where quality allows Water treatment, separate piping

How can data centers reduce water use?

The main options in federal and industry sources:

  1. Run cooling towers at higher cycles of concentration. FEMP says many systems run at two to four cycles, and six or more may be possible. Going from three to six cycles cuts tower make-up water by 20% and blowdown by 50%. The practical limit depends on make-up water quality and the treatment program.
  2. Control blowdown carefully. FEMP identifies blowdown control as the biggest water-saving opportunity in a tower. Conductivity-based controllers and metering on make-up and blowdown lines help.
  3. Use airside economizers. LBNL found that airside economizers let facilities shut down chilled water systems in favorable weather, saving substantial water.
  4. Switch to closed-loop or chip-level cooling. Since August 2024, all new Microsoft data center designs use chip-level cooling with a closed loop that does not evaporate water for cooling. Microsoft estimates this avoids more than 125 million liters a year per data center, with a nominal increase in energy use. Pilot sites in Phoenix and Mt. Pleasant, Wisconsin, are planned for 2026.
  5. Use alternative water for make-up. FEMP lists air handler condensate, once-through cooling water, compatible process effluent, and high-quality recycled water as possible tower make-up sources.
  6. Match cooling to local water risk. Google applies a water risk framework to its data centers, and the results guide its cooling technology choices.
  7. Meter and budget water. Meta reports using water budgeting, flow meter audits, and digital twin models of its cooling systems.

Some operators also fund watershed replenishment: Google reports about 7.7 billion gallons in 2025, about 78% of its freshwater consumption. Replenishment does not reduce what is drawn from the local system.

What compliance comes with each water source?

Every water source a campus uses creates a regulatory relationship. Rules are set state by state. California examples are labeled as such below.

Potable water from a public water system

  • Backflow protection at the service connection. Water suppliers enforce cross-connection control programs set by each state. In California, the State Water Board’s Cross-Connection Control Policy Handbook (CCCPH), in effect since July 1, 2024, lists premises with more than one service connection, an auxiliary water supply such as a well, or recycled water as high hazard (Appendix D).
  • Cooling towers and chillers are not named on the California high hazard list. The water supplier assesses them case by case during its hazard assessment.
  • Testing. In California, assemblies are tested at least annually and after installation or repair, and a failed assembly must be repaired or replaced within 30 days (CCCPH 3.3.3).

Recycled water

  • In California, Title 22 Section 60306 allows cooling towers to use disinfected tertiary recycled water. Where mist can reach people, a drift eliminator and a biocide to control Legionella are required.
  • Dual-plumbed sites in California need an annual inspection and a cross-connection test at least every four years (22 CCR 60316).

Groundwater from an on-site well

  • Under federal rules (40 CFR 141.2), a system that serves water for human consumption to an average of 25 or more people a day for at least 60 days a year, or has 15 or more service connections, is a public water system. Serve the same 25 or more people for more than six months a year and it is a nontransient noncommunity system, with permit, monitoring, and reporting duties.
  • A well connected to a campus that also takes utility water is an auxiliary supply, which California treats as high hazard for backflow purposes.

Construction and new reporting rules

  • Clearing, grading, or excavating one acre or more needs Clean Water Act stormwater permit coverage (40 CFR 122.26(b)(15)).
  • In California, Governor Newsom signed AB 2469, AB 2619, and AB 1577 on September 21, 2026, adding data center water disclosure and reporting requirements. Check the final bill text for effective dates and thresholds.

For a site-by-site map of these obligations, see data center water services.

Frequently asked questions

How much water does a data center use per day? It varies widely by size, cooling system, and climate, so there is no single answer. For scale, Google’s Council Bluffs, Iowa, campus consumed about 1.35 billion gallons in 2025, roughly 3.7 million gallons a day on average.

What is a good WUE for a data center? LBNL puts the U.S. average site WUE just over 0.36 L/kWh through 2023. Microsoft reported 0.30 L/kWh for fiscal year 2024. A lower site WUE can mean higher energy use, so compare WUE together with PUE.

Why do data centers use water instead of air for cooling? Evaporative cooling usually takes less electricity than air-cooled chillers. LBNL and Google both note that water-cooled systems are generally more energy efficient, which is why operators weigh water against energy at each site.

Do data centers use drinking water? Often, yes. Most buy potable water from the local utility. In Google’s 2025 data, about 81% of data center water withdrawals were potable water, with the rest non-potable or reclaimed wastewater.

Do data centers need backflow protection? In most cases, yes. Water suppliers protect the public system through state and local cross-connection programs. California lists premises with more than one service connection, an auxiliary supply such as a well, or recycled water as high hazard.

Talk to an expert

Exodus Water Services plans, permits, operates, and keeps records for the water systems data center campuses depend on: backflow protection and testing, hazard assessments, recycled water use sites, campus wells, and stormwater. Talk to an Expert about your site.